Data Center Specifications

RAISED FLOOR AREA:


Raised Floor: 18,500 sq. ft.

  • 9,500 North Side (27 high)
  • 9,000 South Side (27 high)

OFFICE, STORAGE AND ELECTRICAL:


Office Space & Conference Rooms: 10,000 sq. ft.
Server Build-out Room: 1,500 sq. ft.
Storage: 3,000 sq. ft.
UPS and Electrical Room: 2,500 sq. ft.
Generator Room: 2,000 sq. ft

NETWORK CONTROL:


3,500 sq. ft. NOC (Network Operation Center)

  • Monitored by a 24×7 staff
  • State-of-the-art monitoring solution
  • Remote PDUs and KVMs in all cabinets

UTILITY POWER:


3,000 Amp Main Utility Breaker powered by 3,000 KVA dedicated transformer, with feeds from two substations.

MONITORING SYSTEM:


DataTrax Environmental Control System

UPS:


Redundant UPSs utilizing the Powerware Hot Sync Cabinets including upstream normal and bypass GFI breakers, and Olsen isolation transformers.

  • (4) 500 KVA Powerware units
  • (2) 300 KVA Powerware units

GENERATORS:


(4) Cummins Diesel Generators (redundant w/Kirk-key solution) providing 3.3 Megawatts of power.

  • (2) 650 KW
  • (2) 1,000 KW

AIR CONDITIONING:


A combination of 30 ton, 26 ton, and 20 ton air cooled CRAC units. Providing the computer room with around 7 million BTUs of computer room cooling. Multiple Carrier units provide cooling for the office space and storage rooms.

RACK FEATURES:


APC NetShelter lockable cabinets

  • Each cabinet has two 3 Phase, 208V APC PDUs (Power Strips)
  • Redundant Leibert PDUs

BUILDING SECURITY:


Cameras for internal and external DVR monitoring with motion detectors and card key and keypad access, with after-hours security guard services.

FIRE SAFETY:


High tech fire suppression system, dry pipe pre-action (water) – VESDA monitoring system, under and overhead smoke detectors, heat sensors, and LED control panel for isolating issues.

CARRIERS:


POP/On-Net with AT&T, Verizon, COX, Qwest, TW Telecom, and XO to name a few. The data center is a carrier neutral facility. Multiple carriers use the facility to connect their Orange County and LA County sonet rings. Each provider has redundant entrances and utilizes two separate fiber vaults to enter the building.

CONSTRUCTION:


Purpose Built with steel/acrylic siding and only offices have windows. There are steel pillars that penetrate 20 ft. into the earth for seismic reinforcement.

LOADING DOCK:


6 ton lift which accommodates (1) 53 ft. trailer